At a glance: a refinery in North India replaced the Hydranautics HYDRAcap MAX ultrafiltration modules (105 m², TIPS fibre) in its DM plant pretreatment with Theway Puran Max modules in 2025. The system treats about 4 MLD of refinery effluent ahead of RO, with filtrate turbidity below 1 NTU and SDI below 3.

The installation
Item | Detail |
|---|---|
Plant | Petroleum refinery |
Region | North India |
Application | Pretreatment to RO in the DM plant, about 4 MLD |
Feed water | Treated refinery effluent, turbidity up to 100 NTU, TSS 150 to 200 ppm, SDI above 6 |
Modules replaced | Hydranautics HYDRAcap MAX, 105 m², TIPS fibre |
Theway supply | Puran Max UF modules |
Commissioned | 2025 |
Results
Filtrate turbidity below 1 NTU
Filtrate SDI below 3
No module replaced since commissioning
These figures held over the first six months reported, with feed turbidity up to 100 NTU.


How a direct replacement fits
A Theway direct replacement module is made to the dimensions and connections of the module it replaces, so it goes into the existing rack, couplings and pipework. The plant keeps its frames, valves and controls; only the modules change.
Every HYDRAcap and HYDRAcap MAX model and its Theway replacement is listed in Replacing Hydranautics HYDRAcap UF modules.
Send the make and model of your modules, how many there are and your feed water analysis to mail@thewaymembranes.com, or find your module in the retrofit finder to see the Theway equivalent and its datasheet.
Customer names are not published. Other plants running Theway membranes are listed on our Milestones page.
Specification note: figures are typical values for information only and are not a performance guarantee. Actual performance depends on the feed water, pretreatment and operation. See the product and datasheet disclaimer.