SDI, turbidity and MFI: which RO feed test tells you what

1 hour ago
6 min read

The short answer

Use all three, for different jobs:

  • Turbidity is a fast, continuous, on-line check. It is good for alarms and trends, but it does not see the fine colloids that foul RO elements, so a low reading does not prove the water is clean enough.

  • SDI15 (Silt Density Index over 15 minutes, ASTM D4189) is the number RO element warranties and design guidelines are written around. It is a grab test, it is not linear, and it tops out at 6.67.

  • MFI0.45 (Modified Fouling Index) uses the same filter but records the whole filtration curve. It is proportional to the particle load, so it is the better tool for comparing pre-treatment options and tracking slow change.

Typical RO feed targets are SDI15 below 5 as an upper limit and below 3 for a stable design, with turbidity below 1 NTU and ideally below 0.2 NTU. A well-run ultrafiltration (UF) system typically delivers SDI15 below 2.5 and turbidity below 0.1 NTU, whatever the raw water does.

How SDI15 is measured (ASTM D4189)

The test pushes the feed water through a 0.45 µm membrane filter, 47 mm in diameter, at a constant 207 kPa (30 psi) gauge.

  1. Flush the sample line, then start flow through the filter and time how long it takes to collect the first 500 mL. This is t_i.

  2. Leave the water running through the filter at the same pressure.

  3. At 15 minutes from the start (T = 15), time the collection of another 500 mL. This is t_f.

  4. Calculate the plugging percentage: %P30 = (1 − t_i / t_f) × 100.

  5. Then SDI15 = %P30 / 15.

Practical points that change the result:

  • The ceiling is 6.67. If the filter blocks completely, %P30 reaches 100 and SDI15 = 100 / 15. The standard expects %P30 to stay at or below 75 %; above that, repeat the test over a shorter time (SDI5 or SDI10). Values from different test times are not directly comparable.

  • Pressure and temperature must be steady. A sample that warms during the test filters faster and gives a falsely low reading.

  • Filter pads vary. Pads from different makers, and even different batches, can give different results on the same water. Use one source of pad for a site.

  • Where you sample matters. Measure at the RO feed, after the cartridge filters. Sample ahead of chemicals that can form particles of their own, such as some antiscalant and coagulant combinations, or record where the sample was taken.

Turbidity: fast, cheap and partly blind

Turbidity is measured by the light that particles scatter, usually at 90°. ISO 7027 instruments use infrared light and report in FNU; US EPA Method 180.1 instruments use white light and report in NTU.

An on-line turbidimeter shows a filter breakthrough within minutes, which no grab test can do. Its weakness is what it cannot see. Light scattering depends on particle size, shape and colour. Fine colloids, organic matter and the early stages of biofilm can plug a 0.45 µm pad while scattering very little light. Water at 0.3 NTU can still give an SDI15 above 4, especially after media filtration, where small floc and colloidal iron pass through.

The rule is simple: high turbidity means trouble, but low turbidity does not mean safe. Confirm with SDI or MFI.

MFI: the filtration curve, not two points

The Modified Fouling Index uses the same 0.45 µm filter and the same 207 kPa pressure, but logs the filtrate volume every 30 seconds or so for the whole test. It is now standardised as ASTM D8002.

Plot the time divided by the volume (t/V) against the volume (V). After a short start-up, the line becomes straight; this is cake filtration, where the particles form a layer on the pad. The slope of that straight section, corrected to 20 °C and the reference pressure, is the MFI0.45, in s/L².

Why it is more useful for engineering work:

  • It is linear. MFI is roughly proportional to the concentration of particles that form a cake, so doubling the particle load roughly doubles the MFI. SDI does not behave this way.

  • It has no ceiling. It still works on raw water that would block an SDI pad in minutes.

Typical guidance for RO feed is an MFI0.45 below about 1 to 2 s/L². The weakness is that MFI0.45 still uses a 0.45 µm pad, so it misses colloids much smaller than the pores. Research versions using UF membranes (MFI-UF) capture these, but are not yet routine plant tests.

Worked example: reading an SDI test

Illustrative results from three sample points, with t_i measured at the start and t_f at 15 minutes:

Sample point

t_i (s)

t_f (s)

%P30

SDI15

Turbidity (NTU, typical)

Reading

UF filtrate

30

38

21

1.4

0.05

Good RO feed

Dual-media filtrate

30

60

50

3.3

0.2

Acceptable; fouling allowance needed

Dual-media filtrate, upset

30

150

80

5.3 (invalid)

0.4

%P30 above 75 %: repeat as SDI5 and investigate

Note the third row: turbidity has only doubled, yet the pad is 80 % plugged. Because %P30 exceeds 75 %, the 15-minute value should not be reported as it stands.

Typical values by source, for orientation:

Water

SDI15 (typical)

Turbidity (NTU, typical)

Deep, well-protected borewell

below 2–3

below 0.5

Surface water or open-intake seawater, raw

above 5, often not measurable

1 to above 20

After coagulation and media filtration

3–4, varies with operation

0.1–0.5

After UF

below 2.5, steady

below 0.1

What UF filtrate achieves, and why it is steadier

Media filtrate quality depends on the coagulant dose, the run time and the last backwash. SDI typically creeps up through a run and jumps after a raw-water event.

A UF membrane is a physical barrier with pores around 0.02 to 0.04 µm, far smaller than the 0.45 µm SDI pad. Theway Stream UF PVDF out-in hollow fibre modules typically give filtrate with SDI15 below 2.5 and turbidity below 0.1 NTU, largely independent of raw-water turbidity, as long as the fibres are intact. That steadiness lets the RO be designed for a known, low fouling load.

Two caveats: UF does not remove dissolved organics or nutrients, so RO biofouling is still possible; and filtrate SDI can rise because of growth in an open filtrate tank or particles from chemical dosing after the UF.

What to do

  1. Fit on-line turbidity after each pre-treatment stage and on the RO feed, with alarms.

  2. Run SDI15 at least daily at the RO feed, after the cartridge filters, to ASTM D4189. Record t_i, t_f, temperature and %P30, not just the SDI.

  3. Reject invalid tests. If %P30 is above 75 %, repeat with a shorter time and report it as SDI5 or SDI10.

  4. Use MFI0.45 for design and troubleshooting, for example when comparing media filtration with UF, or tracking a seasonal trend.

  5. Design the RO for the feed quality you actually have. Lower SDI allows a higher flux. Typical seawater RO design flux is about 11 to 14 LMH after conventional media filtration and about 13 to 17 LMH after UF. Run the design in Theway Compass at a conservative flux for your pre-treatment and choose elements from the RO membranes range.

  6. Normalise RO data. Normalised flow and pressure drop show whether fouling is happening. See RO and UF normalisation.

Questions engineers ask

Why is SDI15 limited to 6.67?

Because %P30 cannot exceed 100. A fully plugged pad gives 100 / 15 = 6.67. A result near that ceiling means the water is far too dirty for RO.

Can I convert turbidity to SDI?

No. There is no reliable conversion. The tests see different particles, and the relationship changes between sites and through a filter run.

Is SDI below 5 enough to run an RO plant?

Below 5 is the usual upper limit, not a comfortable operating point. Most designers aim for below 3, and at SDI 3 to 5 the RO should run at a lower flux and be expected to need more frequent cleaning.

My UF filtrate SDI has risen. Is the UF failing?

Check the filtrate turbidity and run a pressure decay or integrity test. If the UF is intact, look downstream: the filtrate tank, the sampling line and any chemicals dosed before the sample point.

Is MFI worth the extra effort?

For daily checks, SDI and turbidity are usually enough. For pre-treatment design, comparing options or investigating unexplained fouling, MFI0.45 gives a more useful, linear number. Send us an enquiry if you would like help reading your results.

Specification note: The figures above are typical or illustrative engineering values for information only and are not a performance guarantee. Test results depend on the method, equipment, filter pads and sampling. Actual RO and UF performance depends on the feed water, pre-treatment, operation and cleaning. See the product and datasheet disclaimer.