Storing RO and UF membranes during a plant shutdown

1 hour ago
6 min read

The short answer

  • Never let a wetted membrane dry out. RO and UF elements that have been in service must stay full of water from the day they stop to the day they restart. Drying causes permanent flux loss.

  • Short stops (up to about 48 hours): flush the concentrate out with permeate or good pretreated feed, keep the vessels full and closed, and flush again every 24 hours.

  • Medium stops (about 2 to 30 days): flush every 1 to 3 days, or preserve. In hot climates, preserving after about 5 days is the safer choice.

  • Long stops (over about 30 days): clean, flush, then fill with sodium metabisulphite (SMBS) solution, typically 1 % for RO and 0.5 to 1 % for UF. Check pH monthly and renew the solution when it falls below 3.

  • Keep stored membranes between about 5 and 35 °C, out of sunlight and free of frost.

  • On restart, flush the preservative to drain, start gently and compare normalised data with the last pre-shutdown values.

Why stopped membranes get worse

A running membrane is swept by crossflow. A stopped one is not. Three things then go wrong.

Biofouling grows. Warm stagnant water, with nutrients left in the feed channels, suits bacteria. The biofilm often shows as a rise in RO pressure drop or a fall in UF permeability after restart.

Scale forms. If the plant stops with concentrate in the last elements, the salts are already near saturation. As the water cools or sits, calcium carbonate, calcium sulphate or silica can come out of solution on the membrane. That is why the first step of any shutdown is to displace concentrate with low-salinity water.

Membranes dry. Polyamide RO and hydrophilised PVDF UF membranes rely on water held in the pore structure. If a vessel drains, or a UF module empties through a leaking valve, the affected part loses flux that cleaning will not bring back.

Preservation with sodium metabisulphite

SMBS (Na₂S₂O₅) is the usual preservative for both RO and UF. It removes dissolved oxygen, which starves aerobic bacteria, and the solution is mildly acidic, which slows growth further.

Typical practice:

  • Use food-grade SMBS, not the cobalt-activated grade sold for boiler oxygen scavenging.

  • Concentration: typically 1 % by weight for RO; 0.5 to 1 % for UF, or as the module instructions state.

  • Make it up in permeate or RO-quality water, never in water containing chlorine or other oxidants.

  • pH: a fresh 1 % solution is around pH 4 to 4.5. SMBS reacts slowly with any oxygen that gets in and turns to sulphate, and the pH falls. When pH drops below about 3, the solution is spent and must be renewed.

  • Exclude air. Fill vessels and modules completely, vent the high points and close all valves. Air pockets use up the SMBS and leave dry spots.

  • Check monthly below about 27 °C and every two weeks above it. Renew the solution at least every 30 days at the lower temperatures, or sooner if the pH or appearance says so.

A cloudy or smelly solution means biological growth has started: drain, clean and preserve again.

Preserve clean membranes only. If the plant was near its cleaning triggers when it stopped, clean first; foulant left on for months is harder to remove. See membrane cleaning limits for typical pH and temperature limits during cleaning.

RO and UF differ in the details

Osmoflux RO elements (8040). Polyamide is damaged by chlorine, so the SMBS must contain no oxidant and the system must be free of chlorine before filling. Fill through the normal feed path with the high-pressure pump off, using a cleaning pump at low pressure. Keep the permeate side full too: close the permeate outlet valves only after the vessels are full, and never apply permeate back-pressure greater than the feed pressure. See RO membranes for the Osmoflux range.

Stream UF modules. Stream modules are PVDF out-in hollow fibre. Before a long stop, run a full clean (typically a caustic and hypochlorite clean, then an acid clean), rinse until the chlorine is gone, then fill the shell side and the filtrate side with SMBS solution. Because each module holds a large volume of fibres, check that the top of every module is full after venting. For short stops, many plants simply run a backwash every 24 hours to keep the fibres wet and refresh the water. See ultrafiltration membranes for the Stream range.

Frost. Water expanding as it freezes can split fibres and damage element housings. If the plant is in a cold location, keep the building heated or ask the supplier about a glycerine-based preservative.

Worked example: how much SMBS

Basis: an illustrative brackish RO train of 6 vessels, each with 6 Osmoflux 8040 elements (36 elements). Allow about 40 L of solution per element, including vessel free volume, pipework and the tank heel. This is a conservative planning figure, not a measured volume.

Item

Value (illustrative)

Elements in train

36

Solution per element (planning allowance)

40 L

Volume to fill vessels and pipework

1,440 L

Batch to make up (with about 40 % margin)

2,000 L

SMBS at 1 % by weight

20 kg

Fresh pH (typical)

about 4 to 4.5

Renew when pH falls below

3

Renewals over a 3-month stop at under 27 °C

about 2

Total SMBS for 3 months (illustrative)

about 60 kg

The same method works for UF: count the modules, take the hold-up volume of the module and its pipework from the module datasheet, add a margin and multiply by the concentration.

What to do

  1. Before the stop, record a full set of operating data. These are the values you will compare with on restart.

  2. Flush out the concentrate with permeate or good pretreated feed at low pressure until the concentrate conductivity is close to the feed.

  3. Decide the storage route by the expected length of the stop and the water temperature.

  4. For long stops, clean, rinse, and fill with SMBS solution. Vent, close the valves and label the skid "Preserved, do not start".

  5. Check pH and appearance at the agreed interval and log the results. Renew when the pH falls below 3.

  6. Keep the plant between about 5 and 35 °C and out of direct sun. In Gulf summers, shade the skid and check more often.

  7. On restart, flush to drain at low pressure for at least 30 minutes to an hour, or until the permeate and concentrate show no SMBS (no sulphite smell and a stable conductivity). Discard all permeate made during this flush.

  8. Start gently. Vent air slowly and raise RO pressure over about a minute to avoid water hammer. For UF, run a pressure decay integrity test before returning the modules to service.

  9. Compare normalised data with the pre-shutdown values using RO and UF normalisation. If flux or salt passage is outside the usual cleaning triggers after 24 to 48 hours, clean.

Dry elements and spares

New RO elements are supplied either dry or wet-preserved in sealed bags. Keep both in their original packaging, in a cool, dry, dark store, typically between 5 and 35 °C, and off the floor.

A dry element can be stored without preservative. Once it has been wetted, it must stay wet.

A wet-preserved element should be checked every few months. If the bag has leaked or the solution looks cloudy, re-bag it in fresh 1 % SMBS.

On first start-up, send the permeate to drain until the preservative has flushed out and quality is stable.

Questions engineers ask

How long can an RO plant stand without flushing?

Typically no more than 24 hours, and less in hot water. A short low-pressure permeate flush each day prevents both scaling and stagnant growth.

Can I preserve membranes with chlorine instead of SMBS?

Not polyamide RO membranes, which chlorine damages. PVDF UF tolerates chlorine during cleaning. Even so, SMBS is the usual preservative for long storage, because the module seals and fittings are not designed for months of contact with oxidants.

Why does the plant produce less water just after restart?

Membranes often show lower flux and slightly higher salt passage in the first hours after preservation. They usually return to their pre-shutdown normalised values within a day of running. If they do not, check for fouling or a drained section.

Do I need to clean before every long shutdown?

Yes, if the plant was showing any fouling. Preserving clean membranes is far easier than recovering fouled ones after months of standing.

What if a vessel has dried out?

Refill it slowly and soak the elements in permeate before restart. Then compare normalised flux with the other vessels. Some flux loss after drying is often permanent. If one vessel falls well below the rest, replace its elements. Send us the data through send an enquiry and we will advise.

Specification note: The concentrations, intervals, temperatures and volumes in this article are typical industry values and an illustrative example, not measurements from any plant. Follow the storage and preservation instructions for your specific elements and modules. This is general guidance and not a performance guarantee. See the product and datasheet disclaimer.