Setting UF backwash and CEB intervals

1 hour ago
6 min read

The short answer

Start from typical values for your feed water, then tune on the plant using transmembrane pressure (TMP):

  • Filtration cycle: typically 20 to 60 minutes. Short for wastewater and seawater, long for clean groundwater and good surface water.

  • Backwash: typically 1.5 to 2.5 times the filtration flux (often 100 to 150 L/m²h) for 30 to 90 seconds, with air scour on out-in fibres such as Stream UF.

  • Chemically enhanced backwash (CEB): sodium hypochlorite for organics and biofouling, typically every 12 hours to every 3 days; acid for iron, manganese and scale, typically every 1 to 7 days.

  • Recovery: the cycle length dominates it. In the illustrative example below, going from a 20-minute to a 60-minute cycle lifts UF recovery from about 89 % to 96 %. Halving the CEB frequency adds only about 0.3 points.

Make the cycle as long as the TMP allows. Set the CEB frequency to hold the TMP baseline, not to chase recovery.

What each step does

Stream UF is an outside-in PVDF hollow fibre. The feed is on the outside of the fibres and the filtrate is inside, so solids collect on the fibre surface and between the fibres. The cleaning steps work at three time scales:

  • Backwash (minutes): filtrate is pushed back through the fibre wall, usually after an air scour that loosens the cake. The shell side is then drained and refilled. This removes most of the reversible fouling: the solids cake built up during the cycle.

  • CEB (hours to days): a backwash with chemical added, a soak of typically 10 to 20 minutes, then a rinse. This removes fouling that a plain backwash leaves behind: organics and biofilm (hypochlorite, sometimes with caustic) or inorganic deposits (acid).

  • Clean-in-place, CIP (weeks to months): a recirculated, heated or longer chemical clean when the CEBs no longer restore the TMP baseline.

A good regime shows a saw-tooth TMP trace: TMP climbs during each cycle, drops back after each backwash, and the post-backwash baseline creeps up slowly until the next CEB resets it. If the baseline still climbs after each CEB, the CEB is too infrequent or uses the wrong chemical. If the TMP rise within a cycle is steep, the cycle is too long or the flux is too high.

Typical values by feed water

Typical starting values for outside-in PVDF UF:

Feed water

Filtration flux (L/m²h)

Cycle (min)

Hypochlorite CEB

Acid CEB

CIP

Groundwater, good surface water (< 5 NTU)

60 to 80

40 to 60

Every 2 to 3 days

Weekly

2 to 3 months

River or lake water (5 to 50 NTU)

50 to 70

30 to 40

Daily to every 2 days

Every 2 to 7 days

1 to 2 months

Seawater, open intake

50 to 70

20 to 40

Every 12 to 24 hours

Every 2 to 7 days

1 to 2 months

Secondary or tertiary effluent

35 to 55

15 to 30

Every 12 to 24 hours

Every 1 to 3 days

Monthly

Typical CEB conditions:

  • Hypochlorite CEB: typically 200 to 500 mg/L free chlorine. In fresh water it is often raised to pH 10 to 12 with caustic to help remove organics. In seawater, avoid caustic: magnesium hydroxide precipitates on the fibres above about pH 9.5. Use hypochlorite on its own, then follow with an acid CEB.

  • Acid CEB: hydrochloric or sulphuric acid to typically pH 2 to 2.5, or citric acid where iron is the main foulant. Increase its frequency where the feed carries iron, manganese or aluminium from a coagulant.

  • Limits: keep pH, temperature and cumulative chlorine exposure within the PVDF limits on our membrane cleaning limits page and the Stream datasheet.

Lower the flux before you shorten the cycle below about 15 minutes.

Worked example: cycle length and recovery

Basis (illustrative):

  • Stream TW 250/1650 modules, 80 m² each, river water feed.

  • Filtration flux 60 L/m²h.

  • Backwash at 120 L/m²h for 60 seconds, with a 2-minute sequence in total (air scour, drain, backwash, refill).

  • One hypochlorite CEB a day, 20 minutes offline, using about four backwash volumes (0.64 m³ per module) for dosing and rinsing.

  • Recovery counts backwash and CEB water only. Shell-side drain losses are excluded for simplicity.

Cycle length

Cycles per day

Filtrate produced (m³/d per module)

Backwash + CEB water (m³/d)

Net filtrate (m³/d per module)

UF recovery

Modules for 100 m³/h net

20 min

64.5

103.3

11.0

92.3

89.4 %

26.0

30 min

44.4

106.5

7.7

98.8

92.7 %

24.3

45 min

30.2

108.8

5.5

103.3

95.0 %

23.2

60 min

22.9

109.9

4.3

105.6

96.1 %

22.7

What the table shows:

  • Recovery follows the volume ratio. Backwash loss is roughly the backwash flux times its duration, divided by the filtration flux times the cycle length: 120 × 1 / (60 × 30) = 6.7 % at a 30-minute cycle. A 20-minute cycle loses 10 %.

  • Cycle length changes the module count. The same 100 m³/h of net filtrate needs about 14 % more membrane area at a 20-minute cycle than at 60 minutes, because of lost filtrate and downtime.

  • CEB frequency barely moves recovery. Running the CEB every second day instead of daily lifts recovery by only about 0.3 points in each row. Its real cost is chemicals, downtime and waste handling, and its real benefit is a stable TMP baseline.

Where the UF feeds an RO, the UF recovery multiplies into the overall plant recovery, and the UF must deliver the RO feed flow. Our UF sizing calculator runs this balance, and Theway Compass covers UF and RO together.

What to do

  1. Start from the feed water. Pick the flux, cycle and CEB frequency from the typical values above for your water type, and size in the coldest month.

  2. Size with the full sequence. Include backwash, CEB and downtime in the module count, not just the filtration flux. Use the UF sizing calculator.

  3. Log TMP, normalised to temperature. Record TMP at the start and end of each cycle and after each CEB. Use RO and UF normalisation so cold-water rises are not mistaken for fouling.

  4. Lengthen the cycle in steps. If the post-backwash TMP returns to baseline, extend the cycle by 5 to 10 minutes and watch for a week.

  5. Set the CEB by the baseline. If the baseline drifts up between CEBs, raise the CEB frequency or switch the chemical (acid if iron or scale, hypochlorite if organics).

  6. Protect the RO. Rinse each CEB fully to drain and confirm chlorine-free filtrate before it reaches polyamide RO membranes.

  7. Ask us. Send your feed analysis through our enquiry form for a review of your Stream UF settings.

Questions engineers ask

How do I know my backwash flux is high enough?

The TMP after each backwash should return close to the start-of-cycle value. If it does not, increase the backwash flux towards 2 to 2.5 times the filtration flux or lengthen the air scour, within the limits on the Stream datasheet.

Should I add chlorine to every backwash?

Many plants add a low dose, typically a few mg/L, on biologically active water to slow biofilm growth between CEBs. It does not replace the CEB.

Why not run a CEB after every cycle?

It would barely change recovery, but it would multiply chemical use, waste volume and fibre exposure to chlorine. Cumulative chlorine exposure counts against membrane life, so use the lowest CEB frequency that holds the TMP baseline.

When is it time for a CIP rather than more CEBs?

When the TMP after a CEB stays clearly above the clean baseline, typically 0.3 to 0.5 bar higher at the same flux and temperature, or when normalised permeability has fallen by about 30 to 40 %. More frequent CEBs rarely recover that.

Does the cycle need to change with the seasons?

Often, yes. Algal blooms, high river turbidity after rain and cold water all raise the TMP. Many plants run shorter cycles and more frequent CEBs in the difficult season and relax them afterwards.

Can a short cycle make up for a high flux?

Only partly. Above the sustainable flux for the water, fouling becomes less reversible and the baseline climbs whatever the cycle length.

Specification note: the figures in this post are typical and illustrative values for design discussion. They are not a performance guarantee for any plant. Actual settings depend on feed water, temperature and operating history, and must stay within the Stream UF datasheet limits. See the product and datasheet disclaimer.