How to read a UF membrane datasheet
Updated: 11 hours ago
At a glance: a UF datasheet gives the membrane (material, MWCO, fibre size, area), the module (housing, caps, potting, flow direction) and the operating limits (feed pressure, transmembrane pressure, backwash pressure, pH, temperature, flux ranges and cycle times). The limits are maximums, not set points, and the pressure limits fall as water temperature rises.

Field by field
The example values are from the TW 250/1650 Stream module.
Field | Example | What it means |
|---|---|---|
Type | Hollow fibre | Fibre geometry; the other main type is flat sheet |
MOC of membrane | PES or PVDF | Membrane polymer; sets chemical and oxidant tolerance |
MOC of body | PVC | Housing material |
Potting material | Proprietary epoxy | Resin that seals fibres into the end caps |
MOC of cap | PVC or PP | End cap material |
MWCO | 100 kDa | Molecular weight cut-off; see kDa unit explained |
Area | 80 m² | Total active membrane area in the module |
Size of fibre | 1.2 mm OD × 0.6 mm ID | Fibre outer and inner diameter |
Flow | Out-in | Feed outside the fibre, filtrate inside; see out-in vs in-out |
Operating mode | Cross flow or dead end | |
Feed pressure | 3 kg/cm² max | Highest pressure the housing and fibre may see |
Transmembrane pressure | 1 kg/cm² max | Highest pressure difference across the membrane |
Backwash pressure | 2 kg/cm² max | Highest pressure on the filtrate side during backwash |
Operating pH | 2 to 11 | Range for continuous operation; cleaning pH is given separately (1 to 13 on Theway hollow fibre UF) |
Operating temperature | 20 to 45 °C | Range of feed temperature |
Feed flux | 20 to 100 L/m²·h | Range of filtration flux; the design value depends on the feed |
Backwash flux | 40 to 150 L/m²·h | Range of reverse flow rate during backwash |
Filtration time | 15 to 60 min | Time between backwashes |
Backwash time | 20 to 60 s | Length of each backwash |
Flushing time | 20 to 60 s | Length of each forward flush |
Units
1 kg/cm² is 98.1 kPa, or 0.981 bar. 1 bar is 100 kPa, or about 14.5 psi. L/m²·h (often written LMH) is litres of filtrate per square metre of membrane per hour.
Temperature derating
Warm water softens polymers, so the allowed pressures fall as temperature rises. For the TW 250/1650:
Water temperature | Maximum system pressure | Maximum TMP | Maximum backflush pressure |
|---|---|---|---|
0 to 20 °C | 300 kPa | 100 kPa | 200 kPa |
20 to 25 °C | 275 kPa | 95 kPa | 175 kPa |
25 to 30 °C | 250 kPa | 90 kPa | 150 kPa |
30 to 35 °C | 225 kPa | 85 kPa | 125 kPa |
35 to 40 °C | 200 kPa | 80 kPa | 100 kPa |
Plants with warm feed water, such as seawater intakes in the Gulf, should design to the hot-season limits.
How to use a datasheet
Design flux sits inside the feed flux range; where it sits depends on the feed water.
Set pump and valve limits below the maximum pressures, allowing for pressure surges.
Check cleaning chemicals against the pH range and the temperature limit.
Set cycle times within the stated ranges, then adjust from operating data.
Questions buyers ask
Is the 100 L/m²·h flux a design value?
No. It is the top of the range. Most plants design well inside it.
Why is feed pressure higher than TMP?
Feed pressure is measured against atmosphere; TMP is the difference between feed and filtrate sides.
Which limit applies if the water warms up during the day?
Design to the limit for the highest temperature the plant will see.
Ask for a datasheet
Datasheets for every Stream and retrofit model are on the Stream UF page and the direct retrofit page. For anything else, use Send Enquiry or mail@thewaymembranes.com.
Specification note: figures are typical values for information only and are not a performance guarantee. Actual performance depends on the feed water, pretreatment and operation. See the product and datasheet disclaimer.