Silt density index (SDI): what it measures and how UF changes it

Nov 12
2 min read

Updated: 11 hours ago

At a glance: the silt density index (SDI) measures how quickly water plugs a 0.45 µm filter. It is the standard check on RO feed water. RO element makers usually set a maximum SDI15 of 5 and prefer below 3. UF filtrate typically measures below 3, which is why UF is used ahead of RO on surface water, seawater and effluents.

Silt density index (SDI): what it measures and how UF changes it

How the test works

The test follows ASTM D4189:

  1. Pass the water through a 47 mm, 0.45 µm membrane filter at a constant 207 kPa (30 psi).

  2. Time how long it takes to collect the first 500 mL: t₁.

  3. Keep the water flowing for 15 minutes.

  4. Time how long it takes to collect another 500 mL: t₂.

  5. Calculate SDI15 = 100 × (1 − t₁ ÷ t₂) ÷ 15.

The highest possible SDI15 is 6.67, when the filter plugs completely. If the filter plugs before 15 minutes, a shorter interval (SDI5 or SDI10) is used.

What the numbers mean

SDI15

What it means for RO feed

Below 3

Generally acceptable; low particle fouling risk

3 to 5

Acceptable to many RO makers, with more frequent cleaning

Above 5

Not suitable for RO without better pre-treatment

Always check the limit your RO element maker sets.

Why UF lowers SDI

UF fibres retain suspended solids, colloids and bacteria, the particles that plug the SDI filter. Media filters and cartridge filters let fine colloids through, especially when the feed turbidity spikes. That is the main reason plants move from media filtration to UF. See UF vs sand and cartridge filters.

Getting a reliable reading

  • Use a dedicated sample point with a short, clean line.

  • Flush the line before each test.

  • Keep pressure steady at 207 kPa.

  • Handle filters with tweezers and do not touch the membrane.

  • Test at the same point and the same time of day.

  • Record water temperature.

Why SDI after UF is sometimes high

  • dirty sample line or sample point

  • biological growth in the filtrate tank or pipework

  • coagulant or other chemicals carried through

  • an integrity breach in a module

Check the sample line and the tank first, then run an integrity test.

Checklist

  • ASTM D4189 method followed

  • Constant 207 kPa

  • Clean, flushed sample line

  • Temperature recorded

  • Results trended, not judged one at a time

Questions buyers ask

Is turbidity enough instead of SDI?

No. Water can have low turbidity and still a high SDI from fine colloids.

Can I measure SDI on raw effluent?

You can, but the filter plugs almost at once. Suspended solids and COD are more useful for effluents.

Does UF filtrate need a cartridge filter before RO?

Many plants keep one as a safety barrier against debris from tanks and pipework.

Plan your RO pre-treatment

Send your feed water data through Send Enquiry or to mail@thewaymembranes.com. See our Stream UF modules and UF as RO pre-treatment.

Specification note: figures are typical values for information only and are not a performance guarantee. Actual performance depends on the feed water, pretreatment and operation. See the product and datasheet disclaimer.