Cooling tower blowdown reuse at a refinery with UF and RO: silica sets the recovery

12 hours ago
5 min read

The short answer

Ultrafiltration followed by brackish water RO recovers cooling tower blowdown as make-up water. UF removes the suspended solids, colloids and bacteria that would foul the RO, and the RO removes the dissolved salts.

The figure that sets the design is silica, not salinity. In the Theway Compass worked example below, blowdown with 120 mg/L of silica allows only 45 % RO recovery. At 46 % the concentrate passes 150 % of silica's solubility, the most an antiscalant normally holds. At the 75 % recovery often assumed for brackish RO, the concentrate would carry 468 mg/L of silica, 318 % of saturation. Compass rejects that design, and calcium sulfate fails as well.

So a plain UF + RO plant returns about 41 % of the blowdown as RO permeate. Going further needs silica removed before the RO.

What is in cooling tower blowdown

A cooling tower concentrates its make-up water by evaporation, typically three to six times, and bleeds off part of the circulating water to keep salts in check. That bleed is the blowdown. It carries:

  • Dissolved salts at three to six times the make-up level: typically 2,000–6,000 mg/L of TDS, rich in calcium, sulfate and silica.

  • Suspended solids and biofilm scrubbed from the air and the tower fill.

  • Treatment chemicals: scale and corrosion inhibitors (phosphonates, polymers, sometimes zinc or phosphate), oxidising biocides (chlorine or bromine) and non-oxidising biocides.

  • Process traces in a refinery: hydrocarbons from heat exchanger leaks, ammonia and organics. TOC is often 10–20 mg/L.

Why UF comes first

RO elements need a feed with a silt density index of 3 or less and no free oil. Blowdown carries enough suspended matter and biological load to foul RO within weeks behind cartridge filters alone. Hollow fibre PVDF UF:

  • gives a filtrate with a stable SDI, whatever the tower is doing upstream;

  • tolerates the oxidising biocides and hydrocarbon traces that would damage RO directly;

  • recovers its permeability by backwash and chemically enhanced backwash (CEB) after upsets.

Free chlorine passes through UF, so remove it before the RO with sodium bisulfite. Polyamide RO membranes tolerate almost none. See Ultrafiltration in refineries and Backwash, CEB and CIP.

Why silica sets the RO recovery

Recovery concentrates everything the RO rejects: with recovery R, the concentrate carries about 1 ÷ (1 − R) times the feed concentration.

At 35 °C and the concentrate pH of about 8.3, Compass puts silica's solubility at 147 mg/L and allows up to 150 % of it with an antiscalant, about 220 mg/L:

RO recovery

Concentrate silica (mg/L)

% of solubility

Compass verdict

45 %

216

148 %

accepted, antiscalant needed

46 %

221

151 %

rejected

75 %

468

318 %

rejected; calcium sulfate also over its limit at 237 %

There are three ways to go higher:

  • Remove silica before the RO, by magnesium oxide or lime softening.

  • Run the RO at high pH after full softening, where silica stays dissolved. A lower pH does not help silica, though it does control calcium carbonate.

  • Reduce the tower's cycles of concentration, so the blowdown carries less silica, at the cost of more blowdown volume.

Each adds cost, so the first step is to find what the plain UF + RO design can reach.

Theway Compass worked example

Basis: refinery cooling tower blowdown at 35 °C, pH 8.2, 15 NTU, TSS 30 mg/L, TOC 15 mg/L. Analysis: Na 750, K 30, Ca 400, Mg 150, Cl 1,360, SO₄ 1,100, HCO₃ 250, NO₃ 20, SiO₂ 120, F 2 mg/L, about 4,200 mg/L of TDS. Compass has "Cooling tower blowdown" as a UF source type and as an RO water class, with flux and cleaning rules set for it.

UF: Sierra 77 PVDF modules, 100 m³/h of net filtrate

Item

Result

Modules

40, in 2 racks of 20 (3,080 m²)

Design flux

40.8 L/m²·h at 20 °C (lowered for TOC 15 mg/L); 32.5 net over the day

Recovery

90.2 % (110.9 m³/h average feed)

Cycle

28 min filtration, 45 s backwash, 30 s forward flush

Cleaning

3 CEBs a day (one extra for the TOC), CIP every 30 days

TMP

0.11 bar at start, 0.17 bar average

Energy

0.016 kWh/m³ for the UF skid

Running cost

₹0.62 per m³ (chemicals and electricity)

RO: brackish Osmoflux BR TW 400 elements, fed with the 100 m³/h of UF filtrate

Item

75 % recovery (rejected)

45 % recovery, two stages (recommended)

Array

19 × 6 + 10 × 6 (174 elements)

12 × 6 + 6 × 6 (108 elements)

Permeate / concentrate (m³/h)

75 / 25

45 / 55

Feed pressure (bar)

9.4

6.8

Permeate TDS (mg/L)

146

84

Concentrate silica

468 mg/L, 318 % of solubility

216 mg/L, 148 %

Calcium sulfate, concentrate

237 % (limit 230 %)

93 %

Specific energy (kWh/m³)

0.51

0.64

Compass verdict

2 errors (silica, calcium sulfate) and 6 warnings

no errors; LSI and TOC warnings (below)

What the example shows:

  • Silica is the hard limit. At 45 % recovery the plant returns 45 m³/h of permeate, about 41 % of the blowdown, or roughly 390,000 m³ a year of make-up water in continuous operation.

  • Use two stages, not one. At 45 %, Compass's first single-stage design (18 × 6) left only 3.1 m³/h of concentrate per vessel, below the 4.1 m³/h minimum for this water class. Splitting it 12 × 6 + 6 × 6 clears that warning for 0.4 bar more feed pressure. Permeate quality is unchanged.

  • The permeate is good make-up water. At 84 mg/L TDS and 2.2 mg/L silica, it suits cooling tower make-up and is good feed for a boiler water demineralisation train.

  • Two warnings remain, and both are real. The concentrate's Langelier index is 2.2, so confirm the antiscalant with the supplier or dose acid to lower the feed pH. And 15 mg/L of TOC will foul RO organically: an activated carbon or biological step ahead of the RO, or a higher cleaning frequency, should be part of the design.

  • The UF is cheap to run. At 0.016 kWh/m³ and ₹0.62/m³, the UF adds little to the cost of the water. The RO's electricity is about ₹5 per m³ of permeate at ₹8/kWh.

Run the same case with your own blowdown analysis in Theway Compass.

Questions engineers ask

Can I send blowdown straight to RO with cartridge filters?

Not reliably. Suspended solids, biofilm and inhibitor residues foul RO quickly. UF gives a steady feed and protects the RO during tower upsets.

Why not run the RO at 75 % recovery like other brackish plants?

Because blowdown is already concentrated in the tower. With 120 mg/L of silica in the feed, 75 % recovery puts 468 mg/L in the concentrate, more than three times its solubility. No standard antiscalant holds that.

How do I raise RO recovery above the silica limit?

Remove silica before the RO by magnesium oxide or lime softening, run a high-pH RO after full softening, or reduce the tower's cycles of concentration. Compare each against the value of the extra water.

Will the biocides damage the UF membranes?

PVDF hollow fibre tolerates the free chlorine levels used in cooling water. Check non-oxidising biocides against the membrane cleaning and chemical limits. Dechlorinate the RO feed.

Can Theway replace the UF modules in an existing blowdown plant?

In most cases, yes. Theway makes drop-in replacements for the main pressurised UF modules. See Direct Retrofit.

Specification and price note: The figures above are estimates from Theway Compass for the stated feed water and design basis, with RO figures at three years of membrane age. They are for information only and are not a performance guarantee. Actual performance depends on the feed water, pre-treatment, operation and cleaning. Costs use the stated assumptions (₹8/kWh and Compass's default chemical costs); they are not Theway prices. See the product and datasheet disclaimer. Ask us for a quotation for your project.

Related: see the ultrafiltration (UF) range and size your plant in Theway Compass.